Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.1

55

Table 3: Log Messages

#

Message

Explanation

01

UPSMAJ

More than 1 UPS Module is sending an alarm or fault warning

02

UPSMIN

Single UPS Module is sending an alarm or fault warning

03

------ N.A.

04

------ N.A.

05

LOADBP

Load is now running on bypass

4

06

VIBRA_

Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to
avoid loading the log filling up.

07

OVTEMP Excess

temperature

08

OUTFLT

No ac output to load

09

BAT-HI

Excessive battery voltage

10

------ N.A.

11

BATEND

End of battery backup. Battery is discharged to shutdown limit

12

BATLOW

Low battery voltage

13

STSWRN

Static Switch Warning or alarm

14

E.P.O.

Emergency Power Off is active

15

EQ-HST

Battery is currently charging in equalizing mode, dc voltage is
temporarily increased

4

Given as a decimal, this is the sum of 8 components each with its own weight:

• Detection of inverter voltage blackout for >3mS – 0 if not detected, 1 of

detected

• Detection of inverter peak voltage <185 V (brownout) - 0 if not detected, 2 if

detected

• Detection of inverter peak voltage high <185 V (brownout) - 0 if not detected,

4 if detected

• Detection of frequency beyond limits (45-65 Hz) - 0 if not detected, 8 if

detected

• Detection of inverter average voltage low - 0 if not detected, 16 if detected
• Detection of inverter average voltage high - 0 if not detected, 32 if detected
• 64 if instruction for load transfer is received from the controller
• 128 if instruction for load transfer is received from the Static Switch


Example:
If LOADBP data is 67, (64 + 2 + 1) this means that 3 components are active:

• Instruction to transfer the load was issued by the controller (64)

• Low peak voltage detected (2)

• Voltage blackout encountered (1)