2 over-voltage protection, Over-voltage protection – MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation

Page 39

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.1

31

5.2 Over-Voltage Protection

CAUTION!
To reduce the risk of fire, connect the UPS only to a circuit
provided with maximum branch circuit over-current protection
as indicated in

Table 1, in accordance with the National Electric

Code, NSI/NFPA 70.

ATTENTION !

Pour réduire le risque du feu, reliez L'UPS seulement à un circuit équipé de
protection maximum de surintensité de circuit de branche comme indiqué
au tableau 1, selon le code électrique national, au NSI/NFPA 70.

Ensure that the lines into and out of the UPS have protective circuit breakers
installed in accordance with the ratings listed in Table 1 for your Power+ model.

Table 1: Required over-current protection

POWER+

Model

Line

Maximum

over-current

protection

Ac input
Ac input bypass
Load

35 A

10 kVA

Battery dc input

30 A

Ac input
Ac input bypass
Load

70 A

20 kVA

Battery dc input

60 A

Ac input
Ac input bypass
Load

110 A

30 kVA

Battery dc input

90 A

Ac input
Ac input bypass
Load

150 A

40 kVA

Battery dc input

125 A

Ac input
Ac input bypass

50 kVA

Load

175 A