Power+ shutdown (switching to bypass), Power, Shutdown (switching to bypass) – MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation

Page 49

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.1

41

3.

Connect the load and observe the results on the display.

4.

Observe that the “dot” bar graph now indicates the load presence and
relative power consumption. Filled dots indicate kW; empty dots indicate
kVA.

POWER+

start-up is now complete.

POWER+ Shutdown (Switching to Bypass)

1.

Switch the load OFF.

2.

Press twice on the On/Off button.

3.

Wait 2 minutes for the POWER+ to shut down. The control screen will
indicate UPS OK (OFF).

Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the
load but in bypass.