POWER+ 3x208 V, User Guide, Release 2.1

6.

POWER+

ROUTINE START

-

UP

This section describes the start-up procedures for the operator after a

POWER+ shutdown.


1.

Press twice on the On/Off button on the upper right of the system
controller panel.

2.

Wait about 2 minutes for the POWER+ to start up.

The following screen is displayed:

Observe that UPS OK indication is now ON and the STSW OK now indicates INV.

If the display continues to indicate BYP, check on the Static Switch panel, that the
inverter is running.

If the inverter indicator on the Static Switch panel is OFF:

● Press the Inv/Byp button on the static switch panel to switch the

inverter ON and wait for the indicator to light.

Press the Inv/Byp button on the lower right of the control panel.

After shutdown, the UPS on,
Alarm
and Load indicators will
flash

.