MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation

Page 56

Advertising
background image

Gamatronic Electronic Industries Ltd.

48

POWER+ 3x208 V, User Guide, Release 2.1

4>

Dry4

Association

Set the alarms that will trigger dry contact number 4

5>

Dry5

Association

Set the alarms that will trigger dry contact number 5

6>

Dry6

Association

Set the alarms that will trigger dry contact number 6

7> Enable / Disable Alarms

Enable or disable specific alarms from the list of 32

6) CALIBRATION


2> Dc-I Offset removal

Set the battery dc current to zero if not calibrated properly, must be

done before the dc-I calibration with disconnected batteries

3>

Dc-I

Calibration


1> Calibrate Battery #1 Current

Set the measurement current for the first battery cabinet

(mA)

2> Calibrate Battery #2 Current

Set the measurement current for the second battery cabinet

(mA)

3> Calibrate Battery #3 Current

Set the measurement current for the third battery cabinet

(mA)

7) PARALLEL/STANDALONE

Set the system operation – stand alone or parallel for more then one UPS

system


9> SC2012

1) Restart Controller

Restart the system controller – will not affect the output voltage

2) Factory Settings

Resets system settings to the default values and restarts the controller –

hard reset, for use on manufacturing stage usually

3) Network…


1> Set IP ADDRESS

Set the IP address for the system communications

2>

Set

GATEWAY

Set the default gateway for the system communications

3>

Set

MASK

Set the subnet mask for the system communications

4>

Store

Store the communication information after changing it

5>

SNMP

Factor

Set the SNMP no communication factor

4) Reset MBX

Reset the communication card