MaxPower Corp Gamatronic Power+ M100 Manuel d'utilisation

Page 55

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.1

47

8) ENABLE/DIS OPTIONS


1>

ENABLE/DISABLE

SHUTDOWN by long ac fail (On/Off)

Enable or disable automatic shutdown after 3 hours of power failure

2> ENABLE/DISABLE Current Sensors

(On/Off)

Enable or disable the usage of battery current sensors

3> ENABLE/DISABLE BATT Temperature sensor

(On/Off)

Enable or disable the usage of battery temperature compensation

sensor




SETUP submenu Option 4: CHARGE

2> Floating Parameters Setup.

Set the actual dc voltage of the system (ups charging voltage)




SETUP submenu Option 5: TIME

● Set the date and the time of the RTC (real time clock) of the controller




SETUP submenu Option 6: SITE

● Set the 6 digit site number for identification through the management software




SETUP submenu Option 7: PASSWORD #1

● Set the 8 character password for entering the SETUP submenu




SETUP submenu Option 8: SERVICE

2> UPSs

Turn selected UPS modules on or off

4> DRYOUT TEST

Test the output dry contacts of the controller

5> CONFIGURE

1) # OF UPSs (redundancy)

Set the number of modules used for redundancy only, which will not be

counted in the global power of the system

2) # OF UPSs (total)

Set the number of UPS modules in the system

3) # Of BATT

Set the number of battery cabinets for the system – 1, 2 or 3

4) Static Switch Setup

Special function, not for customer use!

5) DRY, Alarms

1>

Dry1

Association

Set the alarms that will trigger dry contact number 1

2>

Dry2

Association

Set the alarms that will trigger dry contact number 2

3>

Dry3

Association

Set the alarms that will trigger dry contact number 3