™ SSw

wiittcchhbbooaarrddss

Chapter 2- Installing the Switchboard

99

BBoollttss
Switchboards are furnished with medium carbon steel

hardware with the tensile strengths listed in Table 1.

Similar hardware must be used for any additional

bolting. Use a torque wrench when tightening to the

nominal values given, for either copper or aluminum

connections. Use flat and lock washers for all

connections. Do not place washers under the heads of

carriage bolts.

BBoolltt SSiizzee

TTeennssiillee

SSttrreennggtthh,,

ppssii

TToorrqquuee,, llbb--

fftt

G

Grroosssseeuurr dduu

bboouulloonn

RRééssiissttaannccee

ddee ttrraaccttiioonn,,

ppssii

C

Coouuppllee,, llbb--

ppii

1/4-20

120,000

4

5/16-18

120,000

9

3/8-16

120,000

16

1/2-13

60,000

39

1/2-13 with/avec

21/4" Belleville

washer/rondelle

60,000

70

5/8-16

60,000

80

TTaabbllee 11. Tightening torques for supplied hardware.

EElleeccttrriiccaall CClleeaarraanncceess
Maintain the minimum clearances listed in Table 2 (UL) and

Table 3 (CSA) except at terminals of circuit breakers and

switches.

C

Coonnddiittiioonn

VVoollttaaggee D

Diiffffeerreennccee

D

Diifffféérreennccee ddee tteennssiioonn

00––112255 VV 112266––225500

VV

225511––660000

VV

Between un-insulated

live parts of opposite

polarity

Through air

Over surface

1/2" [13]

3/4" [19]

3/4" [19]

11/4" [31]

1" [25]

2" [51]

Between un-insulated

live parts and grounded

metal through air or

over surface

1/2" [13] 1/2" [13]

1" [25]

TTaabbllee 22.. Minimum clearances for live parts (UL).

A through-air spacing of not less than ½ inch is acceptable

at a circuit breaker or a switch, other than a snap switch,

and between grounded dead metal and insulated neutral of

a 277/480 VAC three-phase, four-wire panel board or

switchboard.



TTaabbllee 33.. Minimum clearances for live parts (CSA).


Where neutral to phase is involved, spacing may be based
on the normal voltage between them. Neutral-to-ground
spacing’s should be based on the same spacing’s required
for the other conductors.

C

Coonnddiittiioonn

VVoollttaaggee D

Diiffffeerreennccee

00––112200 VV 112211––224400

VV

224411––448800

VV

448811––660000

VV

Between un-insulated

live parts of opposite

polarity

Through air

Over surface

1/2" [13]

3/4" [19]

3/4" [19]

11/4" [31]

7/8" [22]

13/4" [44]

1" [25]

2" [51]

Between live parts and

ground

Through air

Over surface

1/2" [13]

3/4" [19]

3/4" [19]

1" [25]

7/8" [22]

11 1/32"

[34]

1" [25]

11/2" [38]