GE Industrial Solutions Evolution Switchboards Manuel d'utilisation

Page 7

Advertising
background image

EEvvoolluuttiioonn SSeerriieess™

™ SSw

wiittcchhbbooaarrddss

Chapter 2- Installing the Switchboard

77

FFiigguurree 55.. Non-walk-in switchboard – outdoor construction.

SSeeiissm

miiccaallllyy CCeerrttiiffiieedd EEqquuiippm

meenntt

For seismically certified switchboards of IBC 2006 & IEEE-

693-2005, follow the previous instructions with the following

modifications. Locate the seismic kit shipped with each

section before installation. The kit for each section is located

in the rear of the switchboard section attached to the

horizontal bus. The kit should contain four 1-inch spacers

per section. These spacers should be installed as shown in

Figure 6 or Figure 7. When floor channels are used, these

spacers should be installed as shown in Figure 8.

FFiigguurree 66.. Installation of seismically certified switchboards

without floor sills.


FFiigguurree 77.. Alternate installation of seismically certified

switchboards without floor sills.

FFiigguurree 88.. Installation of seismically certified switchboards

with floor sills.

FFiieelldd CCoonnnneeccttiioonn aanndd TTeessttiinngg ooff G

Grroouunndd--FFaauulltt

PPrrootteeccttiioonn SSyysstteem

mss

Observe the following points when connecting and testing

ground-fault systems, as illustrated in Figures 9 and 10.

• In the service-entrance section, bond the neutral

conductor to the switchboard ground bus with a main

bonding jumper (ground strap). Locate this grounding

point on the neutral conductor on the

supply side of any

ground-fault sensors involving the neutral conductor.

Do not make grounding connections to the neutral

conductor on the load side of the service disconnect.

• On load feeders, run all phase conductors (and neutral,

if used) through the sensor window(s), with all in the

same direction with respect to sensor polarity.

• Do not run equipment ground conductors through

ground-fault sensors. Connect them directly to the

switchboard ground bus,

not to the neutral bus.

• Connect the service grounding electrode (water pipe,

etc.) to the lug provided on the switchboard ground bus

for this purpose.

• Whenever a service is derived from a grounded neutral

supply, the grounded neutral conductor must be

brought into the service-entrance equipment, even if

the grounded conductor is not needed for the load

supplied by the service. This is required to provide a low-

impedance ground-fault current return path to the

neutral to assure operation of the overcurrent device,

for safety to personnel and property.

• Refer to GE publication GEI-48907 for instructions on

conducting performance test of new installations of

ground-fault protection systems.




Front

Pad without Sills

Pad with Sills

1

5

/

8

Advertising