EEvvoolluuttiioonn SSeerriieess™

™ SSw

wiittcchhbbooaarrddss

Chapter 3- Splicing the Switchboard

2244





The offset neutral bus splice assembly consists of a ‘Z’

shaped bus bar that connects two neutral buses. This offset

splice bar comes braced to the neutral bus from factory.

With the sections previously aligned according to Chapter 4

(Connecting the Section Frames), proceed to detach the bar

from the neutral bus. Next, locate it in place as shown in

figure 32 (Left). Proceed to insert the provided ½”-13 bolts

on left and right holes, and torque accordingly. Refer to

Table 1 for torque value.






















Offset Neutral Bus Splicing

Figure 33 . Left – Splice ready to be positioned in place. Right – Splice in place and

torqued

400A, 600A, 800A, 1000A, 1200A