GE Industrial Solutions Evolution Switchboards Manuel d'utilisation

Page 19

Advertising
background image

EEvvoolluuttiioonn SSeerriieess™

™ SSw

wiittcchhbbooaarrddss

Chapter 3- Splicing the Switchboard

1199



The offset splice assembly consists of two bus bar sets,

already installed from the factory. One of the two sets come

installed on the left-hand section and the other comes

installed on the right-hand section.

With the sections previously aligned according to Chapter 4

(Connecting the Section Frames), proceed to insert the

provided ½”-13 bolts on each phase as shown in Figure 24

and torque accordingly. Refer to

Table 1 for torque value.

These illustrations are applicable for 400A, 600A, 800A,

1000A, 1200A, 1600A, 2000A, 2500A, 3000A & 4000A bus

configurations.

Offset
Splices

Figure 24. Alignment of sections. Sections should be aligned, shown un-aligned for illustration
purposes

Figure 25 . Offset Splice Adjustment Detail

Note: If adjustment is needed to mate left and right splices parts, oblong 2 allows some movement.

Loosen bolts 3, and pull splice bars 4. After that, re-torque bolts 3 according to Table 1 in this manual.

Descriptions

1. Splice Locator
2. Slot in Splice Bar
3. Splice Securing Hardware
4. Offset Splice Bars

Advertising