EEvvoolluuttiioonn SSeerriieess™
™ SSw
wiittcchhbbooaarrddss
Chapter 3- Splicing the Switchboard
2233
FFiigguurree 3322.. Splicing diagram for individually mounted
main/feeder, utility, or incoming lug pull sections to
individually mounted main/feeder utility sections with 5000-
6000 copper neutral bus.
Splices are secured and located hanging vertical on the
neutral bus. To join to the adjacent section, the bolt has to
be removed and the splice rotated 90 degrees to be in
horizontal position to connect to the adjacent neutral bus.
Reinstall bolt and re-torque according to Table 1 in this
manual.
Neutral Bus Splices Continued