Additional Checks for QuietQube Models

Is the lineset length, rise and drop within the
guidelines?

Are the suction and liquid line shut-off valves
open?

Is the line set routed properly?

Are both refrigeration lines to remote
condensing unit run so they do not lay in water
and are properly insulated?

Does the condenser fan motor(s) operate
properly after start-up?

Have all the refrigeration fittings and joints
been leak checked?

Has the condenser/condensing unit been
installed to prevent any roofing damage?

Have the refrigeration lines been insulated and
secured properly to prevent vibration?

Has the RCU remote condensing unit been
located where ambient temperatures will
remain in the range of -20° to 120°F (-29° to
48.9°C)?

Is a refrigeration oil trap (S-trap) installed if the
condenser is installed 21 to 35 feet (6 to 11 m)
above the ice machine head?