Manitowoc Ice RF Manuel d'utilisation

Page 14

Advertising
background image

Section 2

Installation Instructions

Part Number 000007644 3/11

14

Step 6 Leak Check The Refrigeration System

Leak check the new line set connections at the ice
machine head section, condensing unit and S trap as
well as all factory joints throughout the entire system.
Disconnect power to the remote condensing unit. Place
the rocker switch into the ON position. This allows the
low side and high side pressures to equalize for leak
checking. Place the rocker switch in the OFF position.
Connect power to the remote condensing unit and allow
system to pump down after leak checking is complete.

Step 7 Open The Valves Prior To Starting The Ice

Machine

A. Slowly backseat (open-turn counterclockwise)

the suction line shutoff valve.

B. Slowly backseat (open-turn counterclockwise)

the liquid line shutoff valve.

Open Valves

Verify O-ring in schrader valve caps are intact and
reinstall on shutoff valves to prevent refrigerant leakage.
Replace shutoff valve access caps and torque to the
following specifications.

Torque Values

Step 8 Insulation Requirements

To prevent condensation the entire suction line must be
insulated. All insulation must be airtight and sealed at
both ends.

The following insulation requirements prevent
condensation at 90°F (32.2°C) ambient 90% Relative
Humidity. If higher humidity is expected, increase
insulation thickness.

The entire suction line set requires:

Open suction and liquid line

shut-off valves

Important

All refrigeration valve caps must be reinstalled to
prevent future refrigeration leaks.

Stem

18-20 ft. lbs. (24.4-27.1 Nm)

Caps

12-15 ft. lbs. (16.3-20.3 Nm)

Schrader Core

1.5-3 in. lbs. (0.17-0.34 Nm)

Suction Line

Liquid Line

Min. Insulation

Thickness

5/8 in. (16 mm)

3/8 in. (10 mm)

1/2 in. (13 mm)

Suction Line

1/4 in. (7 mm)

Liquid Line

Important

To prevent condensation the entire suction line must
be insulated. All insulation must be airtight and
sealed at both ends.

The minimum requirements are for conditions at or
below 90% humidity and 90°F (32°C) ambient. When
higher humidity will be experienced, or local code
requires, insulation wall thickness will need to be
increased.

Advertising