Installation

12

Gas Connection

PRESSURE REGULATION AND TESTING
MT3855G-G ovens are rated at 150,000 BTU/Hr.

(43.9 kW) (158 MJ) Each oven has been adjusted

at the factory to operate with the type of gas speci-

fied on the rating plate attached to the left side of

the control panel.
Each oven is supplied with a regulator to maintain

the proper gas pressure.

The regulator is essen-

tial to the proper operation of the oven and

should not be removed. It is preset to provide the

oven with 3.5” W.C. (0.87 kPa) for natural gas and

10.5” W.C. (2.50 kPa) for Propane while the flame

is on. The regulator is located on top of the gas

valve, between the manual shutoff and solenoid

valves.
DO NOT INSTALL AN ADDITIONAL REGULATOR

WHERE THE OVEN CONNECTS TO THE GAS

SUPPLY UNLESS THE SUPPLY EXCEEDS THE

MAXIMUM PRESSURE.
NOTE: The minimum gas supply pressure to the

oven is 4.5” W.C. (1.1 kPa) for natural gas

and 11.0” W.C. (2.74 kPa) for Propane gas.

The maximum gas supply pressure to the

oven is 10.5” W.C. (2.61 kPa) for natural gas

and 13” W.C. (3.2 kPa) for Propane gas.

Installation must conform with local codes, or in

the absence of local codes, with the

National Fuel

Gas Code, NFPA54/ANSI Z223.1---Latest Edition,

the Natural Gas Installation Code CAN/CGA-

B149.1 or the Propane Installation Code, CAN/

CGA-B149.2 as applicable.
The oven and its individual shutoff valve must be

disconnected from the gas supply piping system

during any pressure testing of that system at test

pressures in excess of 1/2 psig (3.45kPa).
The oven must be isolated from the gas supply

piping system by closing its individual manual

shutoff valve during any pressure testing of the

gas piping system at test pressures equal or less

than 1/2 psig (3.45kPa).

Gas Connection 5” (127 mm)

Gas Connection 6” (152 mm)