Your new furnace should provide many years of trouble free

performance, however, a yearly inspection of the burners , flue

passageways and the outlet vent assembly should be done. Be

sure all passageways are open and clear of any obstruction, or soot

build up. Be sure to shut off all power to the unit while performing

this inspection.
Periodically remove the circulating air filter and clean with water

to remove all dirt. Shake dry and reinstall in unit.
System Operation

1. This furnace has an electronic thermostat and control board

to monitor the room temperature and then control the furnace

operation to provide the best comfort and performance from a

heating appliance. To operate unit turn ON/OFF switch to ON

and then turn temperature control knob clockwise slowly till

furnace turns on. For typical room comfort, the control knob

should be pointed toward medium.

2. The furnace control board follows sequence of operation which

allows for self diagnosis in the event there is a problem. The

control then blinks a status light, a set number of blinks based

on what problem has been encountered. When the furnace is

on and there is a no fault condition, the red LED is on.

On a typical call for heat by the integral thermostat 24 VAC is

applied to the W terminal on the board.

The inducer blower circuit is energized and the inducer blower

comes on for 15 seconds pre-purging out any gas and closing

the pressure switch.

The hot surface ignitor is energized and after a 17 second warm-

up, the gas valve circuit is energized, opening the gas valve and

igniting the burners. After burning for about 30 seconds, the

circulating air blower comes on, delivering warm air to the room.

If ignition does not occur, the ignition sequence is repeated again

up to 2 more times. (3 trials for ignition-total)

3. After the furnace operates and satisfies the thermostat, the gas

valve closes and the circulating air blower continues to run for

about 2 minutes and then shuts off. The inducer blower runs

for 5 seconds and shuts off.

If for any reason ignition and operation does not occur, the

control board will blink the red fault status LED, a sequence

code, indicating what to look for as a troubleshooting guide.

If the red LED is ON but not blinking check the electronic

temperature control to verify its operation. This can be easily done

by disconnecting the 3 electronic temperature control leads from

the main furnace board and using a pig tail jumper to connect

R & W together on the board. If the furnace comes on and runs

normally the temperature control board is malfunctioning. If

the heater still does not come on, then the main furnace board

is malfunctioning. Look for any fault codes below and verify

the 3 amp fuse is not blown.