Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 99

9424200774 Rev B
93
BE1-11
Tableau de registre
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
59X-3
Mode de
temporisation
SG0
21132
3942*
Uint32
4
L É
s/o
Temporisation constante=0
Temporisation inverse=1
FGIT
59X-3
Enclenchement
SG0
21134
3944*
Float
4
L É
Volt
1 - 150
FGIT
59X-3
Temporisation
SG0
21136
3946*
Float
4
L É
Millisecond
e
50 - 600000
FGIT
59X-3
Coefficient
multiplicateur
SG0
21138
3948*
Float
4
L É
s/o
0 - 9,9
FGIT
59X-3
Mode
SG1
21140
3950*
Uint32
4
L É
s/o
Désactivé=0
3V0=1
V1=2
V2=3
Vx Fondamental=4
Vx 3e harmonique=5
FGIT
Réservé
21142-
45
59X-3
Mode de
temporisation
SG1
21146
3952*
Uint32
4
L É
s/o
Temporisation constante=0
Temporisation inverse=1
FGIT
59X-3
Enclenchement
SG1
21148
3954*
Float
4
L É
Volt
1 - 150
FGIT
59X-3
Temporisation
SG1
21150
3956*
Float
4
L É
Millisecond
e
50 - 600000
FGIT
59X-3
Coefficient
multiplicateur
SG1
21152
3958*
Float
4
L É
s/o
0 - 9,9
FGIT
59X-3
Mode
SG2
21154
3960*
Uint32
4
L É
s/o
Désactivé=0
3V0=1
V1=2
V2=3
Vx Fondamental=4
Vx 3e harmonique=5
FGIT
Réservé
21156-
59
59X-3
Mode de
temporisation
SG2
21160
3962*
Uint32
4
L É
s/o
Temporisation constante=0
Temporisation inverse=1
FGIT
59X-3
Enclenchement
SG2
21162
3964*
Float
4
L É
Volt
1 - 150
FGIT
59X-3
Temporisation
SG2
21164
3966*
Float
4
L É
Millisecond
e
50 - 600000
FGIT
59X-3
Coefficient
multiplicateur
SG2
21166
3968*
Float
4
L É
s/o
0 - 9,9
FGIT
59X-3
Mode
SG3
21168
3970*
Uint32
4
L É
s/o
Désactivé=0
3V0=1
V1=2
V2=3
Vx Fondamental=4
Vx 3e harmonique=5
FGIT
Réservé
21170-
73
59X-3
Mode de
temporisation
SG3
21174
3972*
Uint32
4
L É
s/o
Temporisation constante=0
Temporisation inverse=1
FGIT
59X-3
Enclenchement
SG3
21176
3974*
Float
4
L É
Volt
1 - 150
FGIT
59X-3
Temporisation
SG3
21178
3976*
Float
4
L É
Millisecond
e
50 - 600000
FGIT
59X-3
Coefficient
multiplicateur
SG3
21180
3978*
Float
4
L É
s/o
0 - 9,9
FGIT
59X-4
Mode
SG0
21182
3980*
Uint32
4
L É
s/o
Désactivé=0
3V0=1
V1=2
V2=3
Vx Fondamental=4
Vx 3e harmonique=5
FGIT
Réservé
21184-
87
59X-4
Mode de
temporisation
SG0
21188
3982*
Uint32
4
L É
s/o
Temporisation constante=0
Temporisation inverse=1
FGIT
59X-4
Enclenchement
SG0
21190
3984*
Float
4
L É
Volt
1 - 150
FGIT
59X-4
Temporisation
SG0
21192
3986*
Float
4
L É
Millisecond
e
50 - 600000
FGIT
59X-4
Coefficient
multiplicateur
SG0
21194
3988*
Float
4
L É
s/o
0 - 9,9
FGIT
59X-4
Mode
SG1
21196
3990*
Uint32
4
L É
s/o
Désactivé=0
3V0=1
V1=2
V2=3
Vx Fondamental=4
Vx 3e harmonique=5
FGIT