Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 121
9424200774 Rev B
115
BE1-11
Tableau de registre
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
51-6
Mode de retenue
de tension
SG2
22152
4832*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIT
51-6
Mode
SG3
22154
4834*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIT
51-6
Source
SG3
22156
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIT
51-6
Enclenchement
SG3
22158
4836*
Float
4
L É
Ampère
0,5 - 16
FGIT
51-6
Indice de courbe
SG3
22160
4838*
Uint32
4
L É
s/o
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28
FGIT
51-6
Sens
SG3
22162
4840*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
51-6
Utilisation de la
réinitialisation
instantanée
SG3
22164
4842*
Uint32
4
L É
s/o
Intégrée=0
Instantanée=1
FGIT
51-6
Constante TD
SG3
22166
4844*
Float
4
L É
s/o
0 - 9,9
FGIT
51-6
Constante A
SG3
22168
4846*
Float
4
L É
s/o
0 - 600
FGIT
51-6
Constante B
SG3
22170
4848*
Float
4
L É
s/o
0 - 25
FGIT
51-6
Constante C
SG3
22172
4850*
Float
4
L É
s/o
0 - 1
FGIT
51-6
Constante N
SG3
22174
4852*
Float
4
L É
s/o
0,5 - 2,5
FGIT
51-6
Constante R
SG3
22176
4854*
Float
4
L É
s/o
0 - 30
FGIT
51-6
Consigne de
retenue de
tension
SG3
22178
4856*
Float
4
L É
Volt
30 - 250
FGIT
51-6
Mode de retenue
de tension
SG3
22180
4858*
Uint32
4
L É
s/o
Désactivé=0
Contrôlée=1
Retenue=2
FGIT
51-7
Mode
SG0
22182
4860*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIT
51-7
Source
SG0
22184
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIT
51-7
Enclenchement
SG0
22186
4862*
Float
4
L É
Ampère
0,5 - 16
FGIT
51-7
Indice de courbe
SG0
22188
4864*
Uint32
4
L É
s/o
S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28
FGIT
51-7
Sens
SG0
22190
4866*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
51-7
Utilisation de la
réinitialisation
instantanée
SG0
22092
4868*
Uint32
4
L É
s/o
Intégrée=0
Instantanée=1
FGIT