Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation

Page 173

Advertising
background image

9424200774 Rev B

167

BE1-11

Tableau de registre

Nom

Description

Group

e

Registr

e

Type

Octet

s

Autoris

é en

écriture

Unité

Plage

Style

51-8

Sens

SG2

24740

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

T

51-8

Utilisation de la
réinitialisation
instantanée

SG2

24742

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

T

51-8

Constante TD

SG2

24744

Float

4

L É

s/o

0 - 9,9

T

51-8

Constante A

SG2

24746

Float

4

L É

s/o

0 - 600

T

51-8

Constante B

SG2

24748

Float

4

L É

s/o

0 - 25

T

51-8

Constante C

SG2

24750

Float

4

L É

s/o

0 - 1

T

51-8

Constante N

SG2

24752

Float

4

L É

s/o

0,5 - 2,5

T

51-8

Constante R

SG2

24754

Float

4

L É

s/o

0 - 30

T

51-8

Consigne de
retenue de
tension

SG2

24756

Float

4

L É

Volt

30 - 250

T

51-8

Mode de retenue
de tension

SG2

24758

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

T

51-8

Mode

SG3

24760

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

T

51-8

Source

SG3

24762

Uint32

4

L É

s/o

TC1=0
TC2=1

T

51-8

Enclenchement

SG3

24764

Float

4

L É

Ampère

0,5 - 16

T

51-8

Indice de courbe

SG3

24766

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

T

51-8

Sens

SG3

24768

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

T

51-8

Utilisation de la
réinitialisation
instantanée

SG3

24770

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

T

51-8

Constante TD

SG3

24772

Float

4

L É

s/o

0 - 9,9

T

51-8

Constante A

SG3

24774

Float

4

L É

s/o

0 - 600

T

51-8

Constante B

SG3

24776

Float

4

L É

s/o

0 - 25

T

51-8

Constante C

SG3

24778

Float

4

L É

s/o

0 - 1

T

51-8

Constante N

SG3

24780

Float

4

L É

s/o

0,5 - 2,5

T

51-8

Constante R

SG3

24782

Float

4

L É

s/o

0 - 30

T

51-8

Consigne de
retenue de
tension

SG3

24784

Float

4

L É

Volt

30 - 250

T

51-8

Mode de retenue
de tension

SG3

24786

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

T

51-9

Mode

SG0

24788

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

T

51-9

Source

SG0

24790

Uint32

4

L É

s/o

TC1=0
TC2=1

T

51-9

Enclenchement

SG0

24792

Float

4

L É

Ampère

0,5 - 16

T

Advertising