Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation

Page 115

Advertising
background image

9424200774 Rev B

109

BE1-11

Tableau de registre

Nom

Description

Group

e

Registr

e

Type

Octet

s

Autoris

é en

écriture

Unité

Plage

Style

51-4

Mode de retenue
de tension

SG0

21872
4572*

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

FGIM
T

51-4

Mode

SG1

21874
4574*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

FGIM
T

51-4

Source

SG1

21876

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

51-4

Enclenchement

SG1

21878
4576*

Float

4

L É

Ampère

0,5 - 16

FGIM
T

51-4

Indice de courbe

SG1

21880
4578*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-4

Sens

SG1

21882
4580*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-4

Utilisation de la
réinitialisation
instantanée

SG1

21884
4582*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

51-4

Constante TD

SG1

21886
4584*

Float

4

L É

s/o

0 - 9,9

FGIM
T

51-4

Constante A

SG1

21888
4586*

Float

4

L É

s/o

0 - 600

FGIM
T

51-4

Constante B

SG1

21890
4588*

Float

4

L É

s/o

0 - 25

FGIM
T

51-4

Constante C

SG1

21892
4590*

Float

4

L É

s/o

0 - 1

FGIM
T

51-4

Constante N

SG1

21894
4592*

Float

4

L É

s/o

0,5 - 2,5

FGIM
T

51-4

Constante R

SG1

21896
4594*

Float

4

L É

s/o

0 - 30

FGIM
T

51-4

Consigne de
retenue de
tension

SG1

21898
4596*

Float

4

L É

Volt

30 - 250

FGIM
T

51-4

Mode de retenue
de tension

SG1

21900
4598*

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

FGIM
T

51-4

Mode

SG2

21902
4600*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

FGIM
T

51-4

Source

SG2

21904

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

51-4

Enclenchement

SG2

21906
4602*

Float

4

L É

Ampère

0,5 - 16

FGIM
T

51-4

Indice de courbe

SG2

21908
4604*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-4

Sens

SG2

21910
4606*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-4

Utilisation de la
réinitialisation
instantanée

SG2

21912
4608*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

Advertising