Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation

Page 114

Advertising
background image

108

9424200774 Rev B

Tableau de registre

BE1-11

Nom

Description

Group

e

Registr

e

Type

Octet

s

Autoris

é en

écriture

Unité

Plage

Style

51-3

Indice de courbe

SG3

21824
4526*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-3

Sens

SG3

21826
4528*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-3

Utilisation de la
réinitialisation
instantanée

SG3

21828
4530*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

51-3

Constante TD

SG3

21830
4532*

Float

4

L É

s/o

0 - 9,9

FGIM
T

51-3

Constante A

SG3

21832
4534*

Float

4

L É

s/o

0 - 600

FGIM
T

51-3

Constante B

SG3

21834
4536*

Float

4

L É

s/o

0 - 25

FGIM
T

51-3

Constante C

SG3

21836
4538*

Float

4

L É

s/o

0 - 1

FGIM
T

51-3

Constante N

SG3

21838
4540*

Float

4

L É

s/o

0,5 - 2,5

FGIM
T

51-3

Constante R

SG3

21840
4542*

Float

4

L É

s/o

0 - 30

FGIM
T

51-3

Consigne de
retenue de
tension

SG3

21842
4544*

Float

4

L É

Volt

30 - 250

FGIM
T

51-3

Mode de retenue
de tension

SG3

21844
4546*

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

FGIM
T

51-4

Mode

SG0

21846
4548*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

FGIM
T

51-4

Source

SG0

21848

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

51-4

Enclenchement

SG0

21850
4550*

Float

4

L É

Ampère

0,5 - 16

FGIM
T

51-4

Indice de courbe

SG0

21852
4552*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-4

Sens

SG0

21854
4554*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-4

Utilisation de la
réinitialisation
instantanée

SG0

21856
4556*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

51-4

Constante TD

SG0

21858
4558*

Float

4

L É

s/o

0 - 9,9

FGIM
T

51-4

Constante A

SG0

21860
4560*

Float

4

L É

s/o

0 - 600

FGIM
T

51-4

Constante B

SG0

21862
4562*

Float

4

L É

s/o

0 - 25

FGIM
T

51-4

Constante C

SG0

21864
4564*

Float

4

L É

s/o

0 - 1

FGIM
T

51-4

Constante N

SG0

21866
4566*

Float

4

L É

s/o

0,5 - 2,5

FGIM
T

51-4

Constante R

SG0

21868
4568*

Float

4

L É

s/o

0 - 30

FGIM
T

51-4

Consigne de
retenue de
tension

SG0

21870
4570*

Float

4

L É

Volt

30 - 250

FGIM
T

Advertising