Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation

Page 117

Advertising
background image

9424200774 Rev B

111

BE1-11

Tableau de registre

Nom

Description

Group

e

Registr

e

Type

Octet

s

Autoris

é en

écriture

Unité

Plage

Style

51-5

Indice de courbe

SG0

21964
4656*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-5

Sens

SG0

21966
4658*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-5

Utilisation de la
réinitialisation
instantanée

SG0

21968
4660*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

51-5

Constante TD

SG0

21970
4662*

Float

4

L É

s/o

0 - 9,9

FGIM
T

51-5

Constante A

SG0

21972
4664*

Float

4

L É

s/o

0 - 600

FGIM
T

51-5

Constante B

SG0

21974
4666*

Float

4

L É

s/o

0 - 25

FGIM
T

51-5

Constante C

SG0

21976
4668*

Float

4

L É

s/o

0 - 1

FGIM
T

51-5

Constante N

SG0

21978
4670*

Float

4

L É

s/o

0,5 - 2,5

FGIM
T

51-5

Constante R

SG0

21980
4672*

Float

4

L É

s/o

0 - 30

FGIM
T

51-5

Consigne de
retenue de
tension

SG0

21982
4674*

Float

4

L É

Volt

30 - 250

FGIM
T

51-5

Mode de retenue
de tension

SG0

21984
4676*

Uint32

4

L É

s/o

Désactivé=0
Contrôlée=1
Retenue=2

FGIM
T

51-5

Mode

SG1

21986
4678*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

FGIM
T

51-5

Source

SG1

21988

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

51-5

Enclenchement

SG1

21990
4680*

Float

4

L É

Ampère

0,5 - 16

FGIM
T

51-5

Indice de courbe

SG1

21992
4682*

Uint32

4

L É

s/o

S1=0, S2=1, L1=2, L2=3,
D=4, M=5, I1=6, I2=7,
V1=8, V2=9, E1=10,
E2=11, A=12, B=13, C=14,
G=15, F=16, 46=17, P=18,
T1=19, T2=20, T3=21,
T4=22, A1=23, B1=24,
C1=25, D1=26, E3=27,
F1=28

FGIM
T

51-5

Sens

SG1

21994
4684*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

51-5

Utilisation de la
réinitialisation
instantanée

SG1

21996
4686*

Uint32

4

L É

s/o

Intégrée=0
Instantanée=1

FGIM
T

51-5

Constante TD

SG1

21998
4688*

Float

4

L É

s/o

0 - 9,9

FGIM
T

51-5

Constante A

SG1

22000
4690*

Float

4

L É

s/o

0 - 600

FGIM
T

51-5

Constante B

SG1

22002
4692*

Float

4

L É

s/o

0 - 25

FGIM
T

51-5

Constante C

SG1

22004
4694*

Float

4

L É

s/o

0 - 1

FGIM
T

51-5

Constante N

SG1

22006
4696*

Float

4

L É

s/o

0,5 - 2,5

FGIM
T

51-5

Constante R

SG1

22008
4698*

Float

4

L É

s/o

0 - 30

FGIM
T

51-5

Consigne de
retenue de
tension

SG1

22010
4700*

Float

4

L É

Volt

30 - 250

FGIM
T

Advertising