Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 169

9424200774 Rev B
163
BE1-11
Tableau de registre
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
50-7
Sens
SG0
24564
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
T
50-7
Mode
SG1
24566
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
T
50-7
Source
SG1
24568
Uint32
4
L É
s/o
TC1=0
TC2=1
T
50-7
Enclenchement
SG1
24570
Float
4
L É
Ampère
0,5 - 150
T
50-7
Temporisation
SG1
24572
Float
4
L É
Millisecond
e
0 - 60000
T
50-7
Sens
SG1
24574
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
T
50-7
Mode
SG2
24576
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
T
50-7
Source
SG2
24578
Uint32
4
L É
s/o
TC1=0
TC2=1
T
50-7
Enclenchement
SG2
24580
Float
4
L É
Ampère
0,5 - 150
T
50-7
Temporisation
SG2
24582
Float
4
L É
Millisecond
e
0 - 60000
T
50-7
Sens
SG2
24584
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
T
50-7
Mode
SG3
24586
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
T
50-7
Source
SG3
24588
Uint32
4
L É
s/o
TC1=0
TC2=1
T
50-7
Enclenchement
SG3
24590
Float
4
L É
Ampère
0,5 - 150
T
50-7
Temporisation
SG3
24592
Float
4
L É
Millisecond
e
0 - 60000
T
50-7
Sens
SG3
24594
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
T
50-8
Mode
SG0
24596
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
T
50-8
Source
SG0
24598
Uint32
4
L É
s/o
TC1=0
TC2=1
T
50-8
Enclenchement
SG0
24600
Float
4
L É
Ampère
0,5 - 150
T
50-8
Temporisation
SG0
24602
Float
4
L É
Millisecond
e
0 - 60000
T
50-8
Sens
SG0
24604
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
T