98
9424200774 Rev B
Tableau de registre
BE1-11
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
50-3
Mode
SG3
21380
4132*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-3
Source
SG3
21382
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-3
Enclenchement
SG3
21384
4134*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-3
Temporisation
SG3
21386
4136*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-3
Sens
SG3
21388
4138*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-4
Mode
SG0
21390
4140*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-4
Source
SG0
21392
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-4
Enclenchement
SG0
21394
4142*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-4
Temporisation
SG0
21396
4144*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-4
Sens
SG0
21398
4146*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-4
Mode
SG1
21400
4148*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-4
Source
SG1
21402
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-4
Enclenchement
SG1
21404
4150*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-4
Temporisation
SG1
21406
4152*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-4
Sens
SG1
21408
4154*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-4
Mode
SG2
21410
4156*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-4
Source
SG2
21412
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-4
Enclenchement
SG2
21414
4158*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-4
Temporisation
SG2
21416
4160*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-4
Sens
SG2
21418
4162*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT