Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 102
![background image](/files/773781/content/doc102.png)
96
9424200774 Rev B
Tableau de registre
BE1-11
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
50-1
Sens
SG2
21298
4066*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-1
Mode
SG3
21300
4068*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-1
Source
SG3
21302
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-1
Enclenchement
SG3
21304
4070*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-1
Temporisation
SG3
21306
4072*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-1
Sens
SG3
21308
4074*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-2
Mode
SG0
21310
4076*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-2
Source
SG0
21312
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-2
Enclenchement
SG0
21314
4078*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-2
Temporisation
SG0
21316
4080*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-2
Sens
SG0
21318
4082*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-2
Mode
SG1
21320
4084*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-2
Source
SG1
21322
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-2
Enclenchement
SG1
21324
4086*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-2
Temporisation
SG1
21326
4088*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-2
Sens
SG1
21328
4090*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-2
Mode
SG2
21330
4092*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-2
Source
SG2
21332
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-2
Enclenchement
SG2
21334
4094*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-2
Temporisation
SG2
21336
4096*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-2
Sens
SG2
21338
4098*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT