Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation

Page 101

Advertising
background image

9424200774 Rev B

95

BE1-11

Tableau de registre

Nom

Description

Group

e

Registr

e

Type

Octet

s

Autoris

é en

écriture

Unité

Plage

Style

67

Mode
homopolaire

SG2

21258
4034*

Uint32

4

L É

s/o

VOIN=0

VOIG=1

VXIN=2

VXIG=3

FGIT

67

Mode QVI

SG2

21260
4036*

Uint32

4

L É

s/o

I=1

V=2

VI=3

Q=4

QI=5

QV=6

QVI=7

FGIT

67

Mode

SG3

21262
4038*

Uint32

4

L É

s/o

Désactivé=0
Activé=1

FGIT

Réservé

21264-
65

67

Mode
homopolaire

SG3

21266
4040*

Uint32

4

L É

s/o

VOIN=0

VOIG=1

VXIN=2

VXIG=3

FGIT

67

Mode QVI

SG3

21268
4042*

Uint32

4

L É

s/o

I=1

V=2

VI=3

Q=4

QI=5

QV=6

QVI=7

FGIT

50-1

Mode

SG0

21270
4044*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8

FGIM
T

50-1

Source

SG0

21272

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

50-1

Enclenchement

SG0

21274
4046*

Float

4

L É

Ampère

0,5 - 150

FGIM
T

50-1

Temporisation

SG0

21276
4048*

Float

4

L É

Millisecond
e

0 - 60000

FGIM
T

50-1

Sens

SG0

21278
4050*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

50-1

Mode

SG1

21280
4052*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8

FGIM
T

50-1

Source

SG1

21282

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

50-1

Enclenchement

SG1

21284
4054*

Float

4

L É

Ampère

0,5 - 150

FGIM
T

50-1

Temporisation

SG1

21286
4056*

Float

4

L É

Millisecond
e

0 - 60000

FGIM
T

50-1

Sens

SG1

21288
4058*

Uint32

4

L É

s/o

Sens entrant=0

Sens sortant=1

Non directionnel=2

FGIT

50-1

Mode

SG2

21290
4060*

Uint32

4

L É

s/o

Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9

FGIM
T

50-1

Source

SG2

21292

Uint32

4

L É

s/o

TC1=0
TC2=1

FGIM
T

50-1

Enclenchement

SG2

21294
4062*

Float

4

L É

Ampère

0,5 - 150

FGIM
T

50-1

Temporisation

SG2

21296
4064*

Float

4

L É

Millisecond
e

0 - 60000

FGIM
T