Basler Electric BE1-11 Modbus Protocol Manuel d'utilisation
Page 101

9424200774 Rev B
95
BE1-11
Tableau de registre
Nom
Description
Group
e
Registr
e
Type
Octet
s
Autoris
é en
écriture
Unité
Plage
Style
67
Mode
homopolaire
SG2
21258
4034*
Uint32
4
L É
s/o
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
Mode QVI
SG2
21260
4036*
Uint32
4
L É
s/o
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
67
Mode
SG3
21262
4038*
Uint32
4
L É
s/o
Désactivé=0
Activé=1
FGIT
Réservé
21264-
65
67
Mode
homopolaire
SG3
21266
4040*
Uint32
4
L É
s/o
VOIN=0
VOIG=1
VXIN=2
VXIG=3
FGIT
67
Mode QVI
SG3
21268
4042*
Uint32
4
L É
s/o
I=1
V=2
VI=3
Q=4
QI=5
QV=6
QVI=7
FGIT
50-1
Mode
SG0
21270
4044*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIM
T
50-1
Source
SG0
21272
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-1
Enclenchement
SG0
21274
4046*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-1
Temporisation
SG0
21276
4048*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-1
Sens
SG0
21278
4050*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-1
Mode
SG1
21280
4052*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
FGIM
T
50-1
Source
SG1
21282
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-1
Enclenchement
SG1
21284
4054*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-1
Temporisation
SG1
21286
4056*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T
50-1
Sens
SG1
21288
4058*
Uint32
4
L É
s/o
Sens entrant=0
Sens sortant=1
Non directionnel=2
FGIT
50-1
Mode
SG2
21290
4060*
Uint32
4
L É
s/o
Désactivé=0
IA=1
IB=2
IC=3
3PH=4
3I0=5
I2=6
IG=7
I1=8
Déséquilibre=9
FGIM
T
50-1
Source
SG2
21292
Uint32
4
L É
s/o
TC1=0
TC2=1
FGIM
T
50-1
Enclenchement
SG2
21294
4062*
Float
4
L É
Ampère
0,5 - 150
FGIM
T
50-1
Temporisation
SG2
21296
4064*
Float
4
L É
Millisecond
e
0 - 60000
FGIM
T