APPENDIX I: INPUT WIRING REQUIREMENTS
NOTES
The table above is based on the following output current and voltage: 130VDC @ 60A
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Flexible cable must have an outside diameter of 0.69 inches (17.5 mm) or greater.
Input
P ow er Input
Cur r ent Input
S uggested S izes (S ee Notes)
V oltage
Fr eq.
1-P h
3-P h
1-P h
3-P h
Fuse (Amps)
W ir e (AW G )
W ir e (Canada)
(V olts)
(Hz)
(kV A)
(kV A)
(Amps) (Amps)
1-P h
3-P h
1-P h
3-P h
1-P h
3-P h
208
50/60
12.5
11.2
60
31.1
70
40
4
8
4
8
230
50/60
12.5
11.3
54.1
28.3
70
35
4
8
4
8
240
50/60
12.6
11.4
52.3
27.5
60
35
6
8
6
8
380
50/60
13.9
12.4
36.5
18.9
45
25
8
10
8
10
415
50/60
13.9
12.6
33.4
17.5
40
25
8
12
8
12
460
50/60
13.9
12.7
30.1
16
35
25
8
12
8
12
575
Requires Transform er M odule
Line V oltages with S uggested Circuit P rotection and Wire Sizes
B ased on National E lectric Code and Canadian Electrical Code