54

Rockwell Automation Publication DNET-IN001B-EN-P - January 2012

Appendix A 1756 DeviceNet Status Indicators and Data Structures

Status Structure

The controller receives status information concerning the 1756-DNB scanner
module’s ability to exchange DeviceNet messages with other nodes by reading
from the status structure in the 1756-DNB scanner module. The scanner module
periodically updates the contents of the status structure and copies its contents to
the controller. The status structure consists of several tables. The bit position of
each of the 64-bits that make up a given status table directly corresponds to the
node address of a device.

The status structure consists of these data elements.

Status Structure Element

Description

Data
Type

DINTS

ScanCounter

Counter incremented each I/O scan

32-bit

10

DeviceFailureRegister

Device failed bit table; 1 = failed

64-bit

AutoverifyFailureRegister

Device I/O size does not match scanner’s
internal table; 1 = mismatch

64-bit

DeviceIdleRegister

Device is idle bit table; 1 = idle

64-bit

ActiveNodeRegister

Node online bit table; 1 = online

64-bit

StatusDisplay

ASCII representation of scanner
alphanumeric display

4-byte

ScannerDeviceStatus

Scanner device status

4-byte
binary

11

ScannerAddress

DeviceNet address of1756- DNB scanner
module

8-bit
binary

ScannerStatus

Status of 1756-DNB scanner module

8-bit
binary

ScrollingDeviceAddress

Scrolls through DeviceNet nodes once
per second by address and status; 0 = no
faults

8-bit
binary

ScrollingDeviceStatus

8-bit
binary

ReservedArray

Future expansion (20 bytes)

20 x 8-bit

16

DeviceStatus

DeviceNet node status array, byte per
device

64 x 8-bit

24/32