Install a 1769 DeviceNet Communication Module Chapter 2

Connect the Module to a
DeviceNet Network

Follow these steps to wire the DeviceNet connector.

1.

Connect the DeviceNet cable to the removable connector as shown.

2.

Insert the removable female connector into the mating male connector on
the DeviceNet scanner module.

3.

Screw the removable connector to the scanner case with the upper and
lower mounting screws with a torque of 0.6…0.7 N•m (5…6 lb•in).

Set the Node Address

Set the node address using one of these methods:

For the 1769-ADN, use the node address rotary switches as described in

Set the Node Address of a 1769-ADN Module

.

For the 1769-SDN, use RSNetWorx for DeviceNet software as described

in

Set the Node Address of a 1769-SDN Module

. The 1769-SDN module

has no hardware mechanism to set its address.

DeviceNet Connector

Connect Wire

(1)

(1) DeviceNet cable colors are shown on

the wiring label on the front of the
scanner.

To

Red

V+

White

CAN High

Bare

Shield

Blue

CAN Low

Black

V-

Grounding Screw

Use 2.08 mm

2

(14 AWG) wire

to connect to panel ground.

Comm Adapter

MS

IO

NS

DIAG

DeviceNet Connector

1769-ADN

1769-SDN

IMPORTANT

If the 1769-SDN module is the first or last device connected to the
DeviceNet network trunkline, be sure to add a termination
resistor (120

Ω 1% ≥ ¼W resistor, Allen-Bradley catalog number

1485A-C2) across the blue (CAN Low) and white (CAN High)
wires.