Use rsnetworx for devicenet software, Restore the factory default settings – Rockwell Automation 1769-ADN DeviceNet Modules Installation Instructions Manuel d'utilisation

Page 15

Advertising
background image

Rockwell Automation Publication DNET-IN001B-EN-P - January 2012

15

Install a 1756 DeviceNet Communication Module Chapter 1

Use RSNetWorx for DeviceNet Software

Follow this procedure to use RSNetWorx for DeviceNet software to set the node
address.

1.

In RSNetWorx for DeviceNet software, select the 1756-DNB scanner
module.

2.

From the Tools menu, choose Node Commissioning.

3.

Browse to the DeviceNet network for the 1756-DNB scanner module you
want to commission.

4.

Select the 1756-DNB scanner module you want to commission.

5.

From the Address pull-down menu, choose the node address.

6.

Click Apply.

Restore the Factory Default
Settings

The out-of-box reset will clear the scan list, including ADR configuration
recovery files, and return all software setting attributes to their default values.

Follow this procedure to restore the factory-default communication rate and
node address.

1.

Set the switches to 888.

2.

Restore power to the module.

When the out-of-box reset is complete, the module status display
repeatedly scrolls the message Reset Complete - Change Switch Settings.
During this time, the module does not respond to communication from
any port, including the backplane, DeviceNet connector, or USB port.

3.

After the module resets, perform these steps.
a. Set the switches to the desired position.
b. Restore power to the module.

IMPORTANT

Do not use the 888 switch setting during normal module
operation.