Air flow adjustment maintenance – John Wood Commercial Power Vent - AJWSM Manuel d'utilisation

Page 9

Advertising
background image

8

1. With all exhaust fans and appliance operating as instructed in “Safety

Interlock/Combustion Air Test”, set the Air Flow Adjustment by loosening
locknut and turning rod handle. CAUTION: HANDLE MAY BE HOT, USE
PLIERS TO MOVE HANDLE. Position of rod handle indicates the position
of Air Flow Adjustment inside housing.

2. Using pliers, move handle towards minimum draft setting until spillage is

detected at draft hood relief opening, then re-open Air Flow Adjustment
just enough to eliminate spillage.

3. Lock Air Flow Adjustment at desired setting by tightening locknut.

4. Return appliance, doors, windows, exhaust fans and fireplace dampers to

their previous conditions of use.

1. Both Power Vent Kits GPAK1T-GSW, and GPAK2T-GSW have motors which do not need to be oiled.

2. The owner must semi-annually inspect the Vent Hood and vent pipe for blockage, corrosion and leaks.

3. A vent system inspection must be performed annually by a qualified service agency. The inspection should include the operation

circuit check, safety interlock test, combustion air test and a visual inspection of the complete vent system for corrosion, blockage
or leaks. Any corrosion, blockage or leaks detected must be repaired or replaced immediately.

REPLACEMENT PARTS

DESCRIPTION

PART NUMBER

Power Vent Kit GPAK1T-GSW Vent Hood

VH1-4

Power Vent Kit GPAK2T-GSW Vent Hood

VH1-6

Power Vent Kit GPAK1T-GSW Motor

950-1020

Power Vent Kit GPAK2T-GSW Motor

950-1021

Power Vent Kit GPAK1T-GSW Fan Prover

950-0034

Power Vent Kit GPAK2T-GSW Fan Prover

950-0035

Power Vent Kit GPAK1T-GSW Wheel

950-1011

Power Vent Kit GPAK2T-GSW Wheel

950-1012

Post Purge Relay/Timer (1 to 10 minute adjustable delay)

950-1067

AIR FLOW ADJUSTMENT

MAINTENANCE