INSTALLING OPTIONS AND ACCESSORIES

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

5−12

10. Restart the UPS. See Chapter 7, UPS Operating Instructions," for startup

instructions.

NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton
Customer Service Engineer. Contact an Eaton service representative to schedule a date.

11. Contact an Eaton service representative for verification and testing of the RIM II

and its connections prior to making connections with J1 through J4 (see
Table 5-6 and Figure 5-9).

You can order interface cables separately for connecting to the 15-Pin D-Sub
Connectors.

Table 5-6. J1 through J4 Interface Connectors

Status

J1 through J4

Description

UPS AVAILABLE

Pins 1 and 12

Contacts are closed when the UPS is operating in Normal mode
or ready to supply the load.

UPS OFFLINE

Pins 3 and 13

Contacts are open when the UPS is offline. Contacts are closed
when the UPS is operating in Normal mode.

BATTERY WEAK

Pins 5 and 14

Contacts are closed when approximately two minutes of battery
time remains before the critical load is lost.

UTILITY FAILURE

Pins 6 and 15

Contacts are closed when Utility Failure is detected.

15−Pin D-Sub
Connectors

Figure 5-9. J1, J2, J3, and J4 15−Pin D−Sub Connectors