UNDERSTANDING UPS OPERATION

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

6−8

Input Breaker

(CB1)

(optional)

E1, E2, E3

E6, E7,
E8, E12

NOTE Callout letters

A

,

B

,

C

, and

D

map to Table 3-5 on page 3−10.

NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and there is no neutral conductor
connected at the bypass input, a neutral to ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding jumper.

UPS CABINET

Backfeed

Contactor (K5)

E9,

E10,
E11,

E12

Static

Switch

AC Input to

UPS Rectifier
3 Wire A−B−C

Rotation

AC Input to

Bypass

3 or 4 Wire A−B−C

Rotation

Fuse

Service Connector

Battery

Converter

Inverter

Output

Contactor

(K3)

Fuse

Rectifier

Input

Contactor

(K1)

Battery Contactor (K2)

Fuse

Fuse

Fuse

UPM 2

Battery

Breaker

E4. E5

Battery

Converter

Inverter

Output

Contactor

(K3)

Fuse

Rectifier

Input

Contactor

(K1)

Battery Contactor (K2)

Fuse

Fuse

Fuse

UPM 3

Battery

Breaker

E4. E5

Battery

Breaker

E4. E5

Battery

Converter

Inverter

Output

Contactor

(K3)

Fuse

Rectifier

Input

Contactor

(K1)

Battery Contactor (K2)

Fuse

Fuse

Fuse

UPM 1

Bypass

Breaker

(CB4)

Battery

Converter

Inverter

Output

Contactor

(K3)

Fuse

Rectifier

Input

Contactor

(K1)

Battery Contactor (K2)

Fuse

Fuse

Fuse

UPM 4

X−Slot

Interface

48V Battery

Shunt Trip

Interface Board

Battery Aux

Remote EPO

Building Alarms

Alarm Relays

FI−UPM CABINET

Battery

Breaker

A

B

C

D

C

C

AC Output

to Critical

Load

C

BATTERY SYSTEM

(Not supplied with the UPS)

BATTERY SYSTEM

(Not supplied with the UPS)

BATTERY SYSTEM

(Not supplied with the UPS)

BATTERY SYSTEM

(Not supplied with the UPS)

Figure 6-6. Four UPM UPS System, Output Dual-Feed, Separate Battery System