Powerware 9395 UPS 10001100 kVA Manuel d'utilisation

Page 72

Advertising
background image

UPS SYSTEM INSTALLATION

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

4−28

Table 4-1. TB1, TB2, and TB3 Interface Connections

Terminal TB1

Name

Description

1

REPO NC

Input: Normally-closed dry contact used to activate UPS EPO from a remote switch.

2

REPO Return

3

REPO NO

Input: Normally-open dry contact used to activate UPS EPO from a remote switch.

4

REPO Return

5

Battery Aux

Input: Normally-open contact used to indicate when UPS battery breaker is open or
closed.

6

Battery Aux Common

7

48 Vdc Battery Shunt Trip +

Output: Contacts used to open battery breaker or disconnect.

8

48 Vdc Battery Shunt Trip –

9

Output Contactor K3 NC Aux

Output: Normally-closed contact opens when output contactor closes.

10

Output Contactor K3 NC Aux

Common

Terminal TB2

Name

Description

1

Pull Chain

Output: Backup control for parallel operation.

2

Pull Chain Common

3

Alarm Relay NC

Output: General purpose normally−closed (NC) relay contact.

4

Alarm Relay Common

5

Alarm Relay NO

Output: General purpose normally−open (NO) relay contact.

6

Alarm Relay Common

7

Not Used

8

Not Used

9

Not Used

10

Not Used

Terminal TB3

Name

Description

1

Building Alarm 1

Input: Programmable UPS alarm, activated by a remote dry contact closure.

2

Building Alarm 1 Return

3

Building Alarm 2

Input: Programmable UPS alarm, activated by a remote dry contact closure.

4

Building Alarm 2 Return

5

Building Alarm 3

Default: Charger Off

Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for charger off.

6

Building Alarm 3 Return

7

Building Alarm 4

Default: On Generator

Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for on generator.

8

Building Alarm 4 Return

9

Building Alarm 5

Default: Maintenance Bypass

Input: Programmable UPS alarm, activated by a remote dry contact closure. Default
function set for maintenance bypass.

10

Building Alarm 5 Return

NOTE Return indicates connection to electronics circuit ground. Common" indicates connection to common side of isolated relay contact.

Advertising