UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

3−11

Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and
9395−1100/825 – Common Battery

Basic Unit Rating

Units

Rating 50/60 Hz

kVA

kW

650
591

750
682

825
750

Input and Output Voltage

Volts

480/480

480/480

480/480

AC Input to UPS Rectifier (0.98 Minimum pF)

Full load current plus battery recharge current
(3) Phases, (1) Ground

A

Amps

891

1028

1130

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

AC Input to UPS Bypass (Four Wire)

Full Load Current
(3) Phases, (1) Ground

B

Amps

782

902

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

AC Input to UPS Bypass (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

B

Amps

782

902

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(5)

DC Input from Battery Disconnect to UPS

(1) Positive, (1) Negative

C

Total Amps

1280

1502

1600

Minimum Conductor Size
Number per Pole

AWG or kcmil

(each)

500

(6)

AC Output to Critical Load (Four Wire)

Full Load Current
(3) Phases, (1) Ground

D

Amps

782

902

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(4)

AC Output to Critical Load (Five Wire)

Full Load Current
(3) Phases, (1) Neutral, (1) Ground

D

Amps

782

902

992

Minimum Conductor Size
Number per Phase

AWG or kcmil

(each)

500

(5)

Neutral Bonding Jumper (Four Wire Output Only)

Minimum Conductor Size
Number

AWG or kcmil

(each)

4/0

(1)

NOTE Callout letters

A

,

B

,

C

, and

D

map to Figure 6-7 on page 6−9.