UPS SYSTEM INSTALLATION

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

4−36

12. If required, install wiring from the REPO switch to the trip circuitry of the

upstream protective devices. A second contact block is provided on the REPO
switch for this function (see Figure 4-29). The REPO switch wiring must be in
accordance with NEC Article 725 Class 2 requirements.

13. Reinstall the top internal safety shield panel and secure with the retained

hardware.

14. Reinstall the front door removed in Step 4 and secure with the retained

hardware.

15. Close the door and secure the latch.

Figure 4-31 shows the wiring connections if the normally−closed REPO contacts are
used and Figure 4-32 shows alternative methods of connecting a REPO switch if
using another manufacturer’s switch.

3 (NO)

UPS TB1

REPO

Switch

(NC)

Twisted

Wires

1 (NC)

2 (Return)

4 (Return)

NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE

T

he REPO switch must be a latching−type switch not tied to any other circuits.

NOTE REPO normally−open and normally−closed return terminals are separated on
the terminal board but are electrically in common.

1

2

Figure 4-31. Normally-Closed REPO Switch Wiring