INSTALLING OPTIONS AND ACCESSORIES

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

5−3

Connections for Parallel System Control

Connections for RMP II, RIM II, or SCM II

Alarm

J3

Connections for Bypass Status

Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections

Table 5-1. Powerware Hot Sync CAN Bridge Card Interface Connections

J3 Terminal

Name

Description

1

Alarm

Programmable UPS alarm. Activated by a remote dry contact closure.

2

Alarm Return

3

Alarm Relay NC

Normally-closed contact opens when UPS is on bypass.

4

Alarm Relay Com

Bypass contact return.

5

Alarm Relay NO

Normally-open contact closes when UPS is on bypass.

6

TX

RMP II, RIM II, and SCM II connections.

7

TX

8

CAN L

CAN input for parallel operation.

9

Can H

10

Shield