UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

3−13

Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825

Terminal Function

Terminal

Function

Bus Landing

Tightening Torque

Nm (lb ft)

Stud

AC Input to UPM Section

E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)

E1A (UPM 4 – Four UPM Model)

Phase A

3 – stud mounting

12 (8.3)

M8

E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)

E2A (UPM 4 – Four UPM Model)

Phase B

3 – stud mounting

12 (8.3)

M8

E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)

E3A (UPM 4 – Four UPM Model)

Phase C

3 – stud mounting

12 (8.3)

M8

AC Output from UPM Section

E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)

Phase A

3 – stud mounting

12 (8.3)

M8

E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)

Phase B

3 – stud mounting

12 (8.3)

M8

E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)

Phase C

3 – stud mounting

12 (8.3)

M8

E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)

Neutral

3 – stud mounting

12 (8.3)

M8

DC Input to UPM Section

1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)

Positive

6 – stud mounting

(2 per UPM)

12 (8.3)

M8

1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)

Negative

6 – stud mounting

(2 per UPM)

12 (8.3)

M8

Table 3-9. Supplied Intercabinet Wiring Terminal Hardware Kit

Part

Size

Quantity

Terminals Used On

Eaton Part Number

Flat Washer

M8

36

UPM AC Input, UPM Battery Input, UPM AC

Output, and Neutral

180500036−080

Conical Washer

M8

36

UPM AC Input, UPM Battery Input, UPM AC

Output, and Neutral

180500037−080

Nut

M8

36

UPM AC Input, UPM Battery Input, UPM AC

Output, and Neutral

180200001−05