UPS INSTALLATION PLAN AND UNPACKING

EATON Powerware

®

9395 UPS (1000–1100 kVA) Installation and Operation Manual

S 164201764 Rev 1 www.powerware.com

3−14

Terminals E1 through E12 are 2-hole busbar mountings for standard NEMA 2-hole
barrel lugs. The power wiring connections for this equipment are rated at 90°C. See
Table 3-10 for power cable terminations, Table 3-11 for supplied terminal hardware,
and Table 3-12 for recommended installation parts and tools not supplied by Eaton
Corporation.

Figure 4-18 on page 4−21 and Figure 4-19 on page 4−22 show the location of the
power cable terminals inside the UPS.

Table 3-10. UPS External Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Three UPM
Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825

Terminal Function

Terminal

Function

Bus Landings

(using both sides of bus)

Tightening Torque

Nm (lb ft)

Bolt Size

AC Input to UPS Rectifier

E1

Phase A

6 – 2 bolt mounting

76 (56)

M12

E2

Phase B

6 – 2 bolt mounting

76 (56)

M12

E3

Phase C

6 – 2 bolt mounting

76 (56)

M12

AC Input to Bypass

E6

Phase A

6 – 2 bolt mounting

76 (56)

M12

E7

Phase B

6 – 2 bolt mounting

76 (56)

M12

E8

Phase C

6 – 2 bolt mounting

76 (56)

M12

AC Output to Critical Load

E9

Phase A

6 – 2 bolt mounting

76 (56)

M12

E10

Phase B

6 – 2 bolt mounting

76 (56)

M12

E11

Phase C

6 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Common
Battery

E4

Battery (+)

16 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

16 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI−UPM)

E4

Battery (+)

4 – 2 bolt mounting

76 (56)

M12

E5

Battery (−)

4 – 2 bolt mounting

76 (56)

M12

Input and Output Neutral

E12

Neutral

12 – 2 bolt mounting

22 (16)

M10

Customer Ground

Ground

Ground

15 – 1 bolt mounting

22 (16)

M10

NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in Table 3-13 on page 3−16.