Using Your AVU1500 with a

Home Automation System (optional)

Power Controls (UsagePage=0x86)

Test:

• Write value: Test request value

0: No test

1: Quick test

2: Deep test

3: Abort test

• Read value: Test result value

0: No test initiated

1: Done and Passed

2: Done and Warning (no support needed)

3: Done and Error

4: Aborted

5: In progress

• AudibleAlarmControl: 1: Disable 2: Enable 3: Muted (Temporarily)

Read or Write value: 1: Disabled 2: Enabled 3: Muted (Temporarily)

• DelayBeforeShutdown: Writing this value shuts down the UPS after

the indicated number of seconds.

• The maximum value is 32767. Setting this object to 0 aborts the

countdown. When read, “Delay Before Shutdown” will return the
number of seconds remaining until shutdown, or 0 if no shutdown
countdown is in effect.

• DelayBeforeStartup: Writing this value starts the output after

the indicated number of minutes in “Delay before Startup”. The
maximum value is 32767. Sending this command with 0 aborts
the countdown.

• PowerOnDelay: Delays the UPS startup after power restores. The

power quality may not be stable when power restores; this feature
lets the UPS wait a period of time to start up the system.

Report ID # Usage (usage ID)

Byte #

Unit

Comment

16

}Test (0x58)

1

R/W

17

}Audible Alarm Control (0x5A)

1

R/W

21

}Delay Before Shutdown (0x57)

2

Second

R/W

22

}Delay Before Startup (0x56)

2

Minute

R/W

65

}Power On Delay (0x81)

1

R/W