Registre

Description

Type

Unités

Facteur

d'échelle

L/E

Plage

45778

Protection configurable 1 - Délai
d'activation du seuil 2

Int32

Seconde

s/o

LE 0 - 300

45780

Protection configurable 1 - Seuil
maxi. 1

Int32

s/o

Centi

LE (-99 999 900) - 99 999 900

45782

Protection configurable 1 - Seuil
maxi. 2

Int32

s/o

Centi

LE (-99 999 900) - 99 999 900

45784

Protection configurable 1 - Seuil mini. 1 Int32

s/o

Centi

LE (-99 999 900) - 99 999 900

45786

Protection configurable 1 - Seuil mini. 2 Int32

s/o

Centi

LE (-99 999 900) - 99 999 900

45788

Protection configurable 1 - Type

d'alarme maxi. 1

Int32

s/o

s/o

LE 0 = Statut uniquement

1 = Pré-alarme
2 = Alarme

45790

Protection configurable 1 - Type
d'alarme maxi. 2

Int32

s/o

s/o

LE 0 = Statut uniquement

1 = Pré-alarme

2 = Alarme

45792

Protection configurable 1 - Type

d'alarme mini. 1

Int32

s/o

s/o

LE 0 = Statut uniquement

1 = Pré-alarme

2 = Alarme

45794

Protection configurable 1 - Type

d'alarme mini. 2

Int32

s/o

s/o

LE 0 = Statut uniquement

1 = Pré-alarme
2 = Alarme

45796

Protection configurable 2 - Sélection

des paramètres

Unit32 s/o

s/o

LE Aucun paramètre = 0

P. HUILE = 1

Temp. liquide refroidissement = 2
TENSION BATTERIE = 3

Tr/min = 4
NIVEAU CARBURANT = 5

Hz alternateur = 6
VAB alternateur = 7

VBC alternateur = 8

VCA alternateur = 9
Vmoy LL alternateur = 10

VAN alternateur = 11
VBN alternateur = 12

VCN alternateur = 13
Vmoy LN alternateur = 14

Hz BUS 1 = 15

VAB BUS 1 = 16
VBC BUS 1 = 17

VCA BUS 1 = 18
Vmoy LL bus 1 = 19

VA bus 1 = 20
VB bus 1 = 21

VC bus 1 = 22

Vmoy LN bus 1 = 23
Hz bus 2 = 24

VAB bus 2 = 25
VBC bus 2 = 26

VCA bus 2 = 27
Vmoy LL bus 2 = 28

VAN bus 2 = 29
VBN bus 2 = 30

VCN bus 2 = 31

Vmoy LN bus 2 = 32
PF alternateur = 33

PF BUS 1 = 34
PF BUS 2 = 35

kWH pos. alternateur = 36
kWH nég. alternateur = 37

kWH pos. bus 1 = 38

kWH nég. bus 1 = 39
kWH pos. = 40

kWH nég. bus 2 = 41
IA alternateur = 42

IB alternateur = 43
IC alternateur = 44

I Moy alternateur = 45

IA BUS 1 = 46
IB BUS 1 = 47

IC BUS 1 = 48
Imoy bus 1 = 49

IAN bus 2 = 50
IBN bus 2 = 51

ICN bus 2 = 52

Imoy bus 2 = 53
IG=54

I AUX = 55
kW A alternateur = 56

kW B alternateur = 57
kW C alternateur = 58

kW TOT. alternateur = 59
kW A BUS 1 = 60

Advertising