Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation

Page 243

Advertising
background image

9469370991 Rev A

237

DGC-2020HD

Table des registres par défaut

Nom

Description

Groupe Registre Type Octets L/E

Unité

Plage

51-3

Index de courbe

SG0 3P 23498

Uint32 4

L E s/o

S1 = 0
S2 = 1

L1 = 2

L2 = 3
D = 4

M = 5
I1 = 6

I2 = 7
V1 = 8

V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14
G = 15

F = 16

46 = 17
P = 18

51-3

Sens

SG0 3P 23500

Uint32 4

L E s/o

Entrant = 0

Sortant = 1

Non directionnel = 2

51-3

Utilisation de la réinitialisation
instantanée

SG0 3P 23502

Uint32 4

L E s/o

Intégrée = 0
Instantanée = 1

51-3

Constante TD

SG0 3P 23504

Float

4

L E s/o

0 - 9,9

51-3

Constante A

SG0 3P 23506

Float

4

L E s/o

0 - 600

51-3

Constante B

SG0 3P 23508

Float

4

L E s/o

0 - 25

51-3

Constante C

SG0 3P 23510

Float

4

L E s/o

0 - 1

51-3

Constante N

SG0 3P 23512

Float

4

L E s/o

0,5 - 2,5

51-3

Constante R

SG0 3P 23514

Float

4

L E s/o

0 - 30

51-3

Consigne de limitation en
fonction de la tension

SG0 3P 23516

Float

4

L E Volt

30 - 250

51-3

Mode de limitation en fonction
de la tension

SG0 3P 23518

Uint32 4

L E s/o

Désactivé = 0
Contrôle = 1

Limitation = 2

51-3

Configuration d’alarme

SG0 3P 23520

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

51-3

Échelonnage de ligne basse

SG0 3P 23522

Float

4

L E s/o

0,001 - 3

51-3

Source de limitation en fonction
de la tension

SG0 3P 23524

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

51-3

Constante Q

SG0 3P 23526

Float

4

L E s/o

0,1 - 10

51-3

Mode

SG1 1P 23528

Uint32 4

L E s/o

Désactivé = 0
IA = 1

IB = 2
IC = 3

Imax = 4
3I0 = 5

I2 = 6
IG = 7

I1 = 8

51-3

Source

SG1 1P 23530

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

51-3

Enclenchement

SG1 1P 23532

Float

4

L E Ampère

0,9 - 20

51-3

Index de courbe

SG1 1P 23534

Uint32 4

L E s/o

S1 = 0

S2 = 1
L1 = 2

L2 = 3
D = 4

M = 5

I1 = 6
I2 = 7

V1 = 8
V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14

G = 15
F = 16

46 = 17
P = 18

51-3

Sens

SG1 1P 23536

Uint32 4

L E s/o

Entrant = 0
Sortant = 1

Non directionnel = 2

51-3

Utilisation de la réinitialisation

instantanée

SG1 1P 23538

Uint32 4

L E s/o

Intégrée = 0

Instantanée = 1

Advertising