DGC-2020HD

Table des registres par défaut

Nom

Description

Groupe Registre Type Octets L/E

Unité

Plage

VBC bus 2 = 26
VCA bus 2 = 27

Vmoy LL bus 2 = 28

VAN Bus 2 = 29
VBN bus 2 = 30

VCN bus 2 = 31
Vmoy LN bus 2 = 32

PF alternateur = 33
PF bus 1 = 34

PF bus 2 = 35

kWh positif alternateur = 36
kWh négatif alternateur = 37

kWh positif bus 1 = 38
kWh négatif bus 1 = 39

kWh négatif bus 2 = 40
kWh négatif bus 2 = 41

IA alternateur = 42

IB alternateur = 43
IC alternateur = 44

Imoy alternateur = 45
IA bus 1 = 46

IB bus 1 = 47
IC bus 1 = 48

Imoy bus 1 = 49

IAN bus 2 = 50
IBN bus 2 = 51

ICN bus 2 = 52
Imoy bus 2 = 53

IG = 54
Iaux = 55

kW A alternateur = 56
kW B alternateur = 57

kW C alternateur = 58

kW total alternateur = 59
kW A bus 1 = 60

kW B bus 1 = 61
kW C bus 1 = 62

kW total bus 1 = 63
kW A bus 2 = 64

kW B bus 2 = 65

kW C bus 2 = 66
kW total bus 2 = 67

kVA A alternateur = 68
kVA B alternateur = 69

kVA C alternateur = 70
kVA total alternateur = 71

kVA A bus 1 = 72

kVA B bus 1 = 73
kVA C bus 1 = 74

kVA total bus 1 = 75
kVA A bus 2 = 76

kVA B bus 2 = 77
kVA C bus 2 = 78

kVA total bus 2 = 79
kvar A alternateur = 80

kvar B alternateur = 81

kvar C alternateur = 82
kvar total alternateur = 83

kvar A bus 1 = 84
kvar B bus 1 = 85

kvar C bus 1 = 86
kvar total = 87

kvar A bus 2 = 88

kvar B bus 2 = 89
kvar C bus 2 = 90

kvar total bus 2 = 91
Pression du carburant = 92

Pression de rampe de dosage
de l'injecteur = 93

Carburant total utilisé = 94

Température du carburant = 95
Température de l'huile du

moteur = 96
Température de l'échangeur de

chaleur du moteur = 97
Pression du liquide de

refroidissement = 98

Taux de consommation du
carburant = 99

Pression de compression = 100
Température des pipes

d'admission = 101

Advertising