252

9469370991 Rev A

Table des registres par défaut

DGC-2020HD

Nom

Description

Groupe Registre Type Octets L/E

Unité

Plage

51-5

Index de courbe

SG2 3P 24218

Uint32 4

L E s/o

S1 = 0
S2 = 1

L1 = 2

L2 = 3
D = 4

M = 5
I1 = 6

I2 = 7
V1 = 8

V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14
G = 15

F = 16

46 = 17
P = 18

51-5

Sens

SG2 3P 24220

Uint32 4

L E s/o

Entrant = 0

Sortant = 1

Non directionnel = 2

51-5

Utilisation de la réinitialisation
instantanée

SG2 3P 24222

Uint32 4

L E s/o

Intégrée = 0
Instantanée = 1

51-5

Constante TD

SG2 3P 24224

Float

4

L E s/o

0 - 9,9

51-5

Constante A

SG2 3P 24226

Float

4

L E s/o

0 - 600

51-5

Constante B

SG2 3P 24228

Float

4

L E s/o

0 - 25

51-5

Constante C

SG2 3P 24230

Float

4

L E s/o

0 - 1

51-5

Constante N

SG2 3P 24232

Float

4

L E s/o

0,5 - 2,5

51-5

Constante R

SG2 3P 24234

Float

4

L E s/o

0 - 30

51-5

Consigne de limitation en
fonction de la tension

SG2 3P 24236

Float

4

L E Volt

30 - 250

51-5

Mode de limitation en fonction
de la tension

SG2 3P 24238

Uint32 4

L E s/o

Désactivé = 0
Contrôle = 1

Limitation = 2

51-5

Configuration d’alarme

SG2 3P 24240

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

51-5

Échelonnage de ligne basse

SG2 3P 24242

Float

4

L E s/o

0,001 - 3

51-5

Source de limitation en fonction
de la tension

SG2 3P 24244

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

51-5

Constante Q

SG2 3P 24246

Float

4

L E s/o

0,1 - 10

51-5

Mode

SG3 1P 24248

Uint32 4

L E s/o

Désactivé = 0
IA = 1

IB = 2
IC = 3

Imax = 4
3I0 = 5

I2 = 6
IG = 7

I1 = 8

51-5

Source

SG3 1P 24250

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

51-5

Enclenchement

SG3 1P 24252

Float

4

L E Ampère

0,9 - 20

51-5

Index de courbe

SG3 1P 24254

Uint32 4

L E s/o

S1 = 0

S2 = 1
L1 = 2

L2 = 3
D = 4

M = 5

I1 = 6
I2 = 7

V1 = 8
V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14

G = 15
F = 16

46 = 17
P = 18

51-5

Sens

SG3 1P 24256

Uint32 4

L E s/o

Entrant = 0
Sortant = 1

Non directionnel = 2

51-5

Utilisation de la réinitialisation

instantanée

SG3 1P 24258

Uint32 4

L E s/o

Intégrée = 0

Instantanée = 1

Advertising