Basler Electric DGC-2020HD Modbus Protocol Manuel d'utilisation

Page 231

Advertising
background image

9469370991 Rev A

225

DGC-2020HD

Table des registres par défaut

Nom

Description

Groupe Registre Type Octets L/E

Unité

Plage

51-1

Index de courbe

SG0 3P 22922

Uint32 4

L E s/o

S1 = 0
S2 = 1

L1 = 2

L2 = 3
D = 4

M = 5
I1 = 6

I2 = 7
V1 = 8

V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14
G = 15

F = 16

46 = 17
P = 18

51-1

Sens

SG0 3P 22924

Uint32 4

L E s/o

Entrant = 0

Sortant = 1

Non directionnel = 2

51-1

Utilisation de la réinitialisation
instantanée

SG0 3P 22926

Uint32 4

L E s/o

Intégrée = 0
Instantanée = 1

51-1

Constante TD

SG0 3P 22928

Float

4

L E s/o

0 - 9,9

51-1

Constante A

SG0 3P 22930

Float

4

L E s/o

0 - 600

51-1

Constante B

SG0 3P 22932

Float

4

L E s/o

0 - 25

51-1

Constante C

SG0 3P 22934

Float

4

L E s/o

0 - 1

51-1

Constante N

SG0 3P 22936

Float

4

L E s/o

0,5 - 2,5

51-1

Constante R

SG0 3P 22938

Float

4

L E s/o

0 - 30

51-1

Consigne de limitation en
fonction de la tension

SG0 3P 22940

Float

4

L E Volt

30 - 250

51-1

Mode de limitation en fonction
de la tension

SG0 3P 22942

Uint32 4

L E s/o

Désactivé = 0
Contrôle = 1

Limitation = 2

51-1

Configuration d’alarme

SG0 3P 22944

Uint32 4

L E s/o

Statut uniquement = 0

Pré-alarme = 1
Alarme = 2

51-1

Échelonnage de ligne basse

SG0 3P 22946

Float

4

L E s/o

0,001 - 3

51-1

Source de limitation en fonction
de la tension

SG0 3P 22948

Uint32 4

L E s/o

Alternateur = 0
Bus 1 = 1

Bus 2 = 2

51-1

Constante Q

SG0 3P 22950

Float

4

L E s/o

0,1 - 10

51-1

Mode

SG1 1P 22952

Uint32 4

L E s/o

Désactivé = 0
IA = 1

IB = 2
IC = 3

Imax = 4
3I0 = 5

I2 = 6
IG = 7

I1 = 8

51-1

Source

SG1 1P 22954

Uint32 4

L E s/o

Alternateur = 0

Bus 1 = 1
Bus 2 = 2

51-1

Enclenchement

SG1 1P 22956

Float

4

L E Ampère

0,9 - 20

51-1

Index de courbe

SG1 1P 22958

Uint32 4

L E s/o

S1 = 0

S2 = 1
L1 = 2

L2 = 3
D = 4

M = 5

I1 = 6
I2 = 7

V1 = 8
V2 = 9

E1 = 10
E2 = 11

A = 12
B = 13

C = 14

G = 15
F = 16

46 = 17
P = 18

51-1

Sens

SG1 1P 22960

Uint32 4

L E s/o

Entrant = 0
Sortant = 1

Non directionnel = 2

51-1

Utilisation de la réinitialisation

instantanée

SG1 1P 22962

Uint32 4

L E s/o

Intégrée = 0

Instantanée = 1

Advertising