24

W415-0826 / B / 07.11.11

5.1 MINIMUM CLEARANCE TO COMBUSTIBLES

COMBUSTIBLE FRAMING:
Sides, back, bottom and top
of the appliance

0” to stand-offs

COMBUSTIBLE FINISHING:
Rear

0”

Recessed depth

29 1/2”

Enclosure top

96” from base of appliance

Sides, bottom and top of vent
pipe*

2”

Ceiling

96” from base of appliance

* HORIZONTAL VENT SECTIONS:

A minimum clearance of 2” all around the vent pipe on all horizontal runs to combus-

tibles is required except for clearances in appliance enclosures**. Use fi restop spacer assembly W010-1797 (supplied).

* VERTICAL VENT SECTIONS:

A minimum of 1” all around the vent pipe on all vertical runs to combustibles is

required except for clearances in appliance enclosures**. Use fi restop spacer W615-0075 (not supplied).

**

Horizontal and vertical sections require 5” and 9” clearance from combustibles, respectively. See “MINIMUM

ENCLOSURE CLEARANCES” section.