Napoleon Fireplaces Dream - BGD90 Manuel d'utilisation
Page 24
24
W415-0826 / B / 07.11.11
5.1 MINIMUM CLEARANCE TO COMBUSTIBLES
COMBUSTIBLE FRAMING:
Sides, back, bottom and top
of the appliance
0” to stand-offs
COMBUSTIBLE FINISHING:
Rear
0”
Recessed depth
29 1/2”
Enclosure top
96” from base of appliance
Sides, bottom and top of vent
pipe*
2”
Ceiling
96” from base of appliance
* HORIZONTAL VENT SECTIONS:
A minimum clearance of 2” all around the vent pipe on all horizontal runs to combus-
tibles is required except for clearances in appliance enclosures**. Use fi restop spacer assembly W010-1797 (supplied).
* VERTICAL VENT SECTIONS:
A minimum of 1” all around the vent pipe on all vertical runs to combustibles is
required except for clearances in appliance enclosures**. Use fi restop spacer W615-0075 (not supplied).
**
Horizontal and vertical sections require 5” and 9” clearance from combustibles, respectively. See “MINIMUM
ENCLOSURE CLEARANCES” section.