3.4 VENTING APPLICATION FLOW CHART

13.1

Horizontal Termination

Vertical Termination

Vertical rise is equal

to or greater than

the horizontal run

Vertical rise is less

than horizontal run

Vertical rise is equal

to or greater than

the horizontal run

Vertical rise is less

than horizontal run

Horizontal run +

vertical rise to

maximum of 40 feet

Horizontal run +

vertical rise to

maximum of 24.75

feet

Horizontal run +

vertical rise to

maximum of 40 feet

Horizontal run +

vertical rise to

maximum of 40 feet

4.2 times the

vertical rise equal to

or greater than the

horizontal run

3 times the vertical

rise equal to or

greater than the

horizontal run

3.5 DEFINITIONS

14.1

For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
H

T

- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet

H

R

- combined horizontal vent lengths in feet

H

O

- offset factor: .03 (total degrees of offset - 90°*) in feet

V

T

- combined vertical vent lengths in feet

3.6 ELBOW VENT LENGTH VALUES

15.1

FEET

INCHES

1° 0.03

0.5

15° 0.45 6.0
30° 0.9 11.0
45° 1.35 16.0
90°*

2.7

32.0

* The fi rst 90° offset has a zero value and is shown in the formula as - 90°