Attention! If one of the above procedures results in pressures in excess

of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result

in a hazardous condition.
Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator

in the gas valve. Natural gas models will have a manifold pressure of

approximately 4.0" w.c. (.996kPa) at the valve outlet with the inlet pressure

to the valve from a minimum of 5.0" w.c. (1.24kPa) for the purpose of

input adjustment to a maximum of 10.5" w.c. (2.615kPa). Propane gas

models will have a manifold pressure approximately 10.0" w.c. (2.49kPa)

at the valve outlet with the inlet pressure to the valve from a minimum of

11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum

of 13.0" w.c. (3.237kPa).
A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection,

is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure and full

on in 10 seconds.

Figure 9

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should

be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea

level. For Canadian high altitude applications, this appliance is suitable

for installation at elevations between 0 feet (0m) and 4,500 feet (1,372m)

without change.
Piezo Pilot Ignitor Instructions

Depressing the red button completely causes a spark to occur at the

pilot. This is a substitute for a match which requires opening the pilot

hole cover.
To light the pilot, it is important that the electrode be 1/8" (3mm) from

the thermocouple. The spark must occur at the point the burner flame

hits the thermocouple. The end of the electrode will be red hot with the

pilot on.
On a new installation with air in the gas line, it is suggested that a match

be used. The match will light the pilot faster than the piezo under this

condition.
Proper Pilot Flame

The correct pilot flame (Figure 10) will be blue, extending past the

thermocouple. The flame will surround the thermocouple just below

the tip.
Natural gas pilots require adjusting when the inlet gas pressure is above

5" w.c. (1.245kPa). Remove the pilot cover screw on the control valve

(Figure 9), and turn the adjustment screw clockwise to reduce flame.

Replace pilot cover screw to eliminate gas leakage.
LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper flame.
Proper Main Burner Flame

The correct flame will be a short, blue inner flame with a much larger,

light blue, outer flame. The burner does not have a primary air adjustment.

The flame will be correct if the factory-set pressure and orifice opening

are used. After the furnace has been operating, the burner ports may

be blocked by foreign matter carried in by combustion air. Therefore,

cleaning of the burner may be needed for proper flame.
To clean burner port disconnect the gas supply to the valve, and remove

the screws fastening the burner door. After removing the burner door

from the burner box, remove each main burner. Pilot mounting bracket

will need to be unscrewed and moved out of the way to remove all burners.

Burners can be blown out using compressed air or by blowing through

them. Be sure there is no lint or foreign debris blocking the burner ports.

Reassemble using the same screws earlier removed and locate pilot in

the same position as before and noted above.

Figure 10

Figure 11

Cleaning Combustion (Exchanger) Assembly

A QUALIFIED SERVICE PERSON should remove the combustion

(exchanger) assembly and flue baffles. Apply air pressure to the inside

of the combustion (exchanger) assembly and flue baffles in order to clear

all passageways.