Empire Products FAW-40-1SPP Manuel d'utilisation

Page 4

Advertising
background image

12427-4-0306

Page 4

Figure 1

Outdoor Air

Outlet and inlet air can be brought into the confined space via openings

into a ventilated attic and ventilated crawl space.

Figure 2

Confined Space

Outdoor Air Using Vertical or Horizontal Ducts

If combustion air is taken from outdoors through vertical ducts, the

openings and ducts must have a minimum free area of one square inch

(6.5cm

2

) per 4,000 Btuh of total appliance input. In installations drawing

combustion air from a ventilated attic both air ducts must extend above

the attic insulation.

Figure 3

If combustion air is taken from outdoors through horizontal ducts the

openings and ducts must have a minimum free area of one square inch

(6.5cm

2

) per 2,000 Btuh of total appliance input.

Ventilation and Combustion Air

WARNING: Danger of property damage, bodily injury or death,

this furnace and any other fuel burning appliance must be provided

with enough fresh air for proper combustion and ventilation of

flue gases. Most homes will require that outside air be supplied.

Do not draw air from a corrosive environment such as a workshop

or laundry room.

The requirements for providing air for combustion and ventilation are

listed in the National Fuel Gas Codes NFPA 54/ANSI Z223.1 (in Canada

- CAN/CGA B149).

Note: Air requirements for operation of exhaust fans, kitchen ventilation

systems, clothes dryers, fireplace and any other fuel burning or ventilating

equipment used in the space must be considered in determining combustion

air requirements.
Ventilation Air Openings and Ducts

In determining the free area needed consideration must be given to the

blocking effect of louvers, grills or screens protecting openings.

— If a screen is used to cover openings it must not be smaller than 1/4"

mesh.

— Use the free area of a louver or grill to determine the size opening

required to provide the free area specified. If the free area is not

known assume a 20% free area for wood and a 60% free area for a

metal louver or grill.

— Ducts must have the same cross sectional area as the free area of the

openings to which they connect.

— The minimum dimension of air ducts must not be less than 3

inches.

Installation in an Unconfined Space

An unconfined space is an area including all rooms not separated by

doors with a volume greater than 50 cubic feet per 1,000 Btuh of the

combined total input rates of all appliances which draw combustion air

from that space. For example, a space including a water heater rated at

40,000 Btuh input and a furnace rated at 40,000 Btuh requires a volume of

4,000 cubic feet (50 x (40 + 40) = 4,000) to be considered as unconfined.

If the space has an 8 ft. ceiling, the floor area of the space must be 500

sq. ft. In general, particularly in older homes, a furnace installed in an

unconfined space will not require outside air for combustion. However

in a "tight" newly constructed home, outside air may be necessary to

insure adequate combustion.
Installation in a Confined Space

A confined space is an area with volume less than 50 cubic feet per 1,000

Btuh of the combined input rates of all appliances drawing combustion

air from that space. Small areas such as equipment rooms are confined

spaces. Furnaces installed in a confined space which supply heated air

to areas outside the space must draw return air from outside the space

through tightly sealed return air ducts. A confined space must have 2

openings into the space for combustion air. One opening must be within

12 inches of the ceiling and the other must be within 12 inches of the

floor. The required sizing of these openings is determined by whether

inside or outside air is used to support combustion, the method by which

the air is brought to the space (vertical or horizontal duct) and by the total

input rate of all appliances in the space. See Figure 1.
All Air From Inside — Confined Space

If combustion air is taken from the heated space the 2 openings must

each have a free area of at least one square inch per 1,000 Btuh of total

input of all appliances in the confined space but not less than 100 square

inches (645cm

2

) of free area.

For example: for a 40,000 Btuh furnace only in the confined space each

opening must be 100 square inches (645cm

2

) each of free area.

WARNING: Combustion air must not be drawn from a heated space

which includes exhaust fans, fireplaces or other devices that may

produce a negative pressure in the space.

Advertising
Ce manuel est liée aux produits suivants: