Figure 5

Use U.L. listed gas vent equipment when installing the FAW-40. For

vent pipe running through walls, roof, and within one (1) inch (25mm) of

combustible construction, use B-1 or (B-W) [one inch (25mm) clearance

to combustibles] vent pipe. Type B-2 x 4 or Type B-2 x 6 are to be used

in conjunction with a Listed fire stop spacer.
Be sure baseplate is attached to top of furnace before inserting unit into

recessed wall installation.
Installing Optional Side Outlets

Side outlet register,

SOR-1 may be installed on one or both sides of the

furnace at the required clearances of 18 inches (457mm) to adjacent wall

or combustible material as shown in Figure 6.

1. Turn "OFF" all electric power to the furnace.

2. Remove the front panel from the furnace.

3. Remove the (2) #8 x 3/8" (9mm) screws that attach the inner shield

cover plate to the inner shield.

4. Scribe a line between the four dimples on the outer casing side to form

a square.

5. Drill a pilot hole within the scribed square on the outer casing. Remove

the sheet metal within the scribed square with a tin snips or comparable

tool. Attention! Do not cut the electrical wires located between the outer

casing and the inner shield.

6. Insert the 5" x 5" (127mm x 127mm) inner boot through the outer cas-

ing. Align the clearance holes on the inner boot with the screw holes

on the inner shield. Attach inner boot to inner shield with (2) # 8 x 3/8"

(9mm) screws removed in Step 3.

7. Place the register over the 5 1/2" (140mm) square opening with the

louvers set for the desired direction and mark the mounting holes using

the register as a template.

8. Drill (2) 1/8" diameter holes in cabinet side and attach the register with

(2) #10 x 1" (25mm) provided screws.

9. Installation of SOR-1 is completed.
Side outlet kit,

SOK-1, 10" (254mm) boot assembly with register, for

warm air discharge into an adjoining room may be installed on either side

of the furnace at the required clearance of 4 inches (102mm) to adjacent

wall as shown in Figure 6.
To install SOK-1, please use Steps 1 through 5 in the SOR-1 instructions

for FAW-40 furnaces. Now, use the following Steps to complete installa-

tion of the SOK-1.

1. Using the inner and outer boots as hole templates, mark and drill (4)

1/8" (3mm) diameter holes in the inner shield and (4) 1/8" (3mm)

diameter holes in the cabinet side.

2. Locate and cut a 6 3/4" (171mm) square opening through wall.

3. Attach furnace to wall (see Attaching Furnace to Wall).

4. With furnace in place, after checking alignment of side outlet opening

in wall and furnace, place the 9 3/8" x 9 3/8" (238mm x 238mm) side

outlet wall plate over outer boot, pass the outer boot through the wall

and attach side wall plate to furnace side of wall with (2) #10 x 1 1/2"

(38mm) provided screws.

5. Attach outer boot to the cabinet side with (4) #8 x 1/4" (6mm) provided

screws.

6. Position and attach inner boot to inner shield with (4) #8 x 1/4" (6mm)

provided screws.

7. Place the register over the 6 3/4" (171mm) square opening with the louvers

positioned for the desired discharge direction and mark the mounting

holes using the register as a template.

8. Drill (2) 1/8" (3mm) diameter holes in the wall and attach the register

with (2) #10 x 1 1/2" (38mm) provided screws.

9. Installation of SOK-1 is completed.

Figure 6

Installing Optional Rear Outlet

Rear outlet kit, 10" (254mm) boot assembly with register, ROK-1 for warm

air discharge into an adjoining room.
Attention: Before furnace is attached to the wall, the wall opening for the

rear outlet must be cut, in addition to removal of the outer and inner casing

knockouts on furnace.

1. The wall opening measurements for the rear outlet are the following.

A. From floor to bottom of wall opening is 10 11/16" (271mm).

B. From bottom of wall opening to top of wall opening is 8 1/2"

(216mm).

C. Wall opening width is 12 1/8" (308mm).

2. Scribe a line between the four dimples on the outer casing back to form

a square. Drill a pilot hole within the scribed square on the outer casing

back. Remove the sheet metal within the scribed square with a tin snips

or comparable tool.

3. Remove the (4) #8 x 3/8" (9mm) screws that attach the inner casing

close off plate to the inner casing.

4. Insert the privacy shield through the outer casing back and the inner

casing back. The privacy shield will be in front of the inner casing back

and behind the combustion chamber tubes. Align clearance holes on

privacy shield with screw holes on inner casing back. Attach privacy

shield to inner casing back with (2) #8 x 3/8" (9mm) provided. Attention:

The (2) #8 x 3/8" (9mm) screws must be inserted from the front of

the furnace.

5. Attach furnace to wall.

6. Align clearance holes on 8" x 12" (203mm x 305mm) boot with screw

holes on outer casing back and mark boot to be flush with wall surface.

Remove boot and cut to proper length.

7. Attach 8" x 12" (203mm x 305mm)boot to outer casing back with (6)