Ip system troubleshooting sequence – Empire Products FAW-40-1SPP Manuel d'utilisation

Page 14

Advertising
background image

12427-4-0306

Page 14

START

IP SYSTEM TROUBLESHOOTING SEQUENCE

Turn OFF Gas Supply

Disconnect System Control

Harness

Set Thermostat to Call for

Heat

Check for Proper Voltage at

Control Harness (See InsetA-

Voltage Should be 24V

Between Thermostat and 24V

Common, and 24V Between

24VCommon and 24VHot.)

Plug Harness into SmartValve

Control

Wait for Internal Check Delay

(SV9501)

Igniter Warms UP and Glows

Red

Note: Igniter Will Cycle OFF

and Back ON Once During the

90 Second IgnitionTrial

Turn On Gas Supply

Pilot Burner Lights

MainValve Opens and

Main Burner Lights

System is Okay

Check

Line Voltage Power

Low Voltage Transformer

Limit Controller

Thermostat

Wiring

Unplug Pilot Burner Cable.

Measure Voltage at SmartValue HSI

Element Output (See Inset B) 24V

Nominal

Replace Igniter/Flame Rod

Assembly

Reconnect Pilot Burner Cable

Check that Pilot Gas is Flowing

Wait to Assure Pilot Gas Tubing is

Purged.

Measure Voltage Between 24V Hot

and 24V Common Leads to

SmartValve Control. Must Measure

at Least 19.5 VAC with Igniter

Powered. See Inset A to Identify

Proper Lead. This Check Must be

Done with the SmartValve Control

Connected and Igniter Powered.

Replace Igniter/Flame Rod

Assembly

Check that Pilot Flame Makes

Good Contact with Pilot Burner

Flame Rod

Check for Good Electrical

Connection Through the Pilot

Tubing

If Both of the Above are Good,

Replace Igniter/Flame Rod

Cycle Thermostat OFF and Back

ON

Main Burner Lights

YES

NO

NO

NO

NO

YES

YES

YES

Replace SmartValve Control

Reconnect Pilot Burner Cable

NO

Replace SmartValve Control

NO

Check Transformer and Line Volt

Supply

NO

Replace SmartValve Control

NO

SmartValve System Troubleshooting Sequence

Note: Before Troubleshooting, Become Familiar

with the Sequence of Operation

TM

HSI

Terminals

INSET B

End View

of Control

Harness

Connector

EFT

Output

24 Volt

Hot

24

Volts

24 Volt

Common

24

Volts

24 Volt

Thermostat

INSET A

Advertising